- Solenoid Coil System 13 ATEX with terminal box
Wideth: 52mm
Protection by encaps:
EX Ⅱ 2 G Ex e mb ⅡC T4, T6 Gb
EX Ⅱ 2 D Ex tb mb ⅢC T130°C, T80°C Db IP65, IP67
Connection Type: Terminal Box
Moulding Material: Thermoplastic
- General Data
Voltage tolerance: +/-10%
Ambient temperature: -40°C bis + 50°C/ + 60°C
Relative Duty Cycle: 100%
Insulation Class of Insulating Materials
According to DIN VDE 0580: F
Degree of Protection: IP65 / IP67
Type Examination Certificate: PTB 11 ATEX 2027 X
Imprint: nass magent (customer imprint possible)
- Drawing
- Specification
MODEL | PIPE SIZE | CV | ORIFICE | FLUID TEMP. (ºC) |
Operating Pressure kgf-cm2 (bar) | VACUUM (Torr) |
Dimension (mm) |
Weight (kg) |
||||||
WATER | AIR | STEAM | LIGHT OIL | GAS | L | H | D | |||||||
SKW-15 | 1/2" | 4.5 | 15mm | -5ºC~+70ºC | 0~5 | 0~7 | 0~5 | 0~10-3 | 70 | 133 | 62 | 1.04 | ||
SKW-20 | 3/4" | 8.6 | 20mm | -5ºC~+70ºC | 0~5 | 0~7 | 0~5 | 0~10-3 | 73 | 140 | 62 | 1.16 | ||
SKW-25 | 1" | 12 | 25mm | -5ºC~+70ºC | 0~5 | 0~7 | 0~5 | 0~10-3 | 100 | 147 | 62 | 1.76 | ||
SKW-35 | 1-1/4" | 24 | 35mm | -5ºC~+70ºC | 0~5 | 0~7 | 0~5 | 0~10-3 | 130 | 178 | 62 | 3.39 | ||
SKW-40 | 1-1/2" | 28 | 40mm | -5ºC~+70ºC | 0~5 | 0~7 | 0~5 | 0~10-3 | 130 | 183 | 62 | 3.49 | ||
SKW-50 | 2" | 48 | 50mm | -5ºC~+70ºC | 0~5 | 0~7 | 0~5 | 0~10-3 | 165 | 191 | 62 | 5.08 |
- Material
PARTS | Coil | Tube | Spring | Core | Plug | Diaphragm | Valve Body |
MATERIAL | NASS Explosion-proof Coil | Stainless Steel | Stainless Steel | Stainless Steel | Viton | NBR | Stainless Steel |
- Description
- SKW series is direct, multiplex, connected diaphragm, conductive, and normally close (NC) 2/2 solenoid valve
- Explosion-proof Protection Level: Ⅱ2 G Ex e mb ⅡC T4 Gb
- Waterproof Protection: IP67
- Able to be operated directly under low pressure
- Availability of fluid: water, air, light oil, gas, vacuum
- Acceptable for customization VITON, Silicone, EDPM for diaphragm (only available for SKW-20 and SKW-25)
- Cautions
- Before installation depressurize the piping system and clean internally.
- For the protection of the equipment install a strainer or filter suitable for the service involved in the inlet side as close to the solenoid valve as possible.
- Ambient temperature should be under 70ºC
- Operating temperature should be under 60ºC
- AC voltage tolerance: +/- 10%; DC voltage tolerance: +/- 1%
- All standard solenoid valve MUST be mounted vertically upright.
- Not suitable for fluid as below:
- Liquid status when it is at high temperature; solid status when it is cool.
- Corrosive fluid
- Seawater
- Viscosity over 20cst